Product Description

Xenex Control Panel Specifications

ORDER CODES

2 ZONE CONVENTIONAL PANEL, EN54 LESS BATTERIES 13270-02LB
4 ZONE CONVENTIONAL PANEL, EN54 LESS BATTERIES 13270-04LB
8 ZONE CONVENTIONAL PANEL, EN54 LESS BATTERIES 13270-08LB
SPECIFICATION

NO. OF ZONES 2 4 8
MAXIMUM LOAD PER ZONE 3mA

NO. OF SOUNDER CIRCUITS 2 4 8

MAX. SOUNDER CIRCUIT LOAD 500mA per circuit max 1A combined

BATTERIES 2 x 12V, 2.1 Ah min 2 x 12V, 2.1 Ah min 2 x 12V, 3.4 Ah

BATTERY STANDBY 72 hours (1mA per zone + 0.5A sounder load max)

CABLE TYPE BS 6387, 2 core, min 1.5mm2 CSA

OPERATING ENVIRONMENT Indoor, 0 - 40ºC