Fire Alarm System and Panel Specifications
.
.
Fire Alarm system with panel get now
2 ZONE CONVENTIONAL PANEL, EN54 including BATTERIES
4 ZONE CONVENTIONAL PANEL, EN54 including BATTERIES
8 ZONE CONVENTIONAL PANEL, EN54 including BATTERIES
SPECIFICATION
NO. OF ZONES 2, 4, 8 MAXIMUM LOAD PER ZONE 3mA
NO. OF SOUNDER CIRCUITS 2, 4, 8 MAX.
SOUNDER CIRCUIT LOAD 500mA per circuit max 1A combined
BATTERIES 2 x 12V, 2.1 Ah min 2 x 12V, 2.1 Ah min 2 x 12V, 3.4 Ah
BATTERY STANDBY 72 hours (1mA per zone + 0.5A sounder load max)
CABLE TYPE BS 6387, 2 core, min 1.5mm2 CSA
OPERATING ENVIRONMENT Indoor, 0 – 40ºC
CLASS CHANGE FACILITY Volt free contact – max distance 100m